Publication Details

Leveraging the SRTP protocol for over-the-network memory acquisition of a GE Fanuc Series 90-30

KARPÍŠEK, F.; BAGGILI, I.; BREITINGER, F. Leveraging the SRTP protocol for over-the-network memory acquisition of a GE Fanuc Series 90-30. Digital Investigation, 2017, vol. 2017, no. 22, p. 26-38. ISSN: 1742-2876.
Czech title
Leveraging the SRTP protocol for over-the-network memory acquisition of a GE Fanuc Series 90-30 č
Type
journal article
Language
English
Authors
Karpíšek Filip, Ing.
Baggili Ibrahim (FIT)
Breitinger Frank (FIT)
and others
URL
Keywords

GE Fanuc Series 90-30, Live memory acquisition, GE-SRTP protocol SCADA, PLC

Abstract

Programmable Logic Controllers (PLCs) are common components implemented across many industries such as manufacturing, water management, travel, aerospace and hospitals to name a few. Given their broad deployment in critical systems, they became and still are a common target for cyber attacks; the most prominent one being Stuxnet. Often PLCs (especially older ones) are only protected by an outer line of defense (e.g., a  firewall) but once an attacker gains access to the system or the network, there might not be any other defense layers. In this scenario, a forensic investigator should not rely on the existing software as it might have been compromised. Therefore, we reverse engineered the GE-SRTP network protocol using a GE Fanuc Series 90-30 PLC and provide two major contributions: We first describe the Service Request Transport protocol (GE-SRTP) which was invented by General Electric (GE) and is used by many of their Ethernet connected controllers. Note, to the best of our knowledge, prior to this work, no publicly available documentation on the protocol was available affording users' security by obscurity. Second, based on our understanding of the protocol, we implemented a software application that allows direct network-based communication with the PLC (no intermediate server is needed). While the tool's forensic mode is harmless and only allows for reading registers, we discovered that one can manipulate/write to the registers in its default configuration, e.g., turn off the PLC, or manipulate the items/processes it controls.

Published
2017
Pages
26–38
Journal
Digital Investigation, vol. 2017, no. 22, ISSN 1742-2876
DOI
UT WoS
000407728500004
EID Scopus
BibTeX
@article{BUT144472,
  author="Filip {Karpíšek} and Ibrahim {Baggili} and Frank {Breitinger}",
  title="Leveraging the SRTP protocol for over-the-network memory acquisition of a GE Fanuc Series 90-30",
  journal="Digital Investigation",
  year="2017",
  volume="2017",
  number="22",
  pages="26--38",
  doi="10.1016/j.diin.2017.06.005",
  issn="1742-2876",
  url="http://www.sciencedirect.com/science/article/pii/S1742287617301925"
}
Files
Back to top